Crane Common Troubleshooting Solutions
Symptom  | Probable Causes  | Sugguested Remedy  | |
1  | When the knife switch on the protective disc is closed, the fuse of the operating circuit is burnt out.  | A phase in the control circuit h is grounded  | Clear the grounding  | 
2  | When the main contactor is closed, the fuse on the lead-in wire is burnt out.  | This phase is grounded  | Clear the grounding  | 
3  | After the controller starts turning, the current relay makes action.  | 1. The setting values of the overcurrent relay are inconsistent 2. A certain link of the mechanical part is stuck  | 1. Adjust the relay current to be 225-250% of the rated current of the motor 2. Check the mechanical part  | 
4  | The motor cannot reach the rated power, and rotation is slow.  | 1. The brake is not completely released 2. Voltage drops in the circuit 3. Resistor wiring is wrong  | 1. Check and adjust the brake mechanism 2. Eliminate the reason why the voltage drop value exceeds the standard 3. Connect the resistor wiring  | 
5  | The corresponding motor is not powered off when the terminal switch lever makes action.  | 1. Short circuit occurs in the circuit of the end switch 2. The order of the wires connected to the controller is disordered  | 1. Check the conductor leading to the terminal switch 2. Check wiring  | 
6  | The contactor does not fall off after the power is turned off.  | 1. Grounding or short circuit of the operating circuit 2. The contactor contact is welded 3. The contact surface of the armature iron is stuck by the oil stain  | 1. Find the damaged place with the megohmmeter and then handle it 2. Eliminate the error of the contactor being welded 3. Eliminate the oil stain on the contact surface  | 